SKU: EU/CO/CO/TSCONCTP100

Conductivity Controller, 220V (ECTSCONCTP1002) (01X216018)

Pre-order

RM 5,353.00

Pre-order

Alpha COND 1000 panel-mount Conductivity controller/transmitter with 220 VAC setting. Incl. terminal blocks, gasket, threaded rods, catch, etc

Product Features

The Alpha COND 1000 features up to ten selectable conductivity ranges and corresponding cell constant K values, easily configured through a six-button keypad. Adjustable temperature co-efficient and ultrapure water compensation option allow measurements in broad-range applications, from ultrapure water to high-conductivity samples.

:: ±1% full scale accuracy across ten different Conductivity ranges

:: Adjustable temperature coefficient from
0.0 to 10.0% for higher accuracy

:: Pure water compensation option corrects non-linearity of pure water temperature correction curves in ultrapure water applications

:: Option of Auto or Manual Temperature Compensation. Three-wire system compensates for cable-length resistance errors

:: Meter displays electrode information after each successful calibration. Previous calibration data is retained in the event of unsuccessful calibrations

:: Line adjustment feature corrects long cable resistance errors – an important feature useful in applications involving high conductivity measurements

:: Galvanically-isolated, scaleable 0/4 to 20 mA output for high-quality output on peripheral devices

Product Specification

Description
Conductivity
Range… to 1.999 µS/cm ; … to 19.99 µS/cm ;
… to 199.9 µS/cm ; … to 1999 µS/cm ;
… to 5000 µS/cm ; … to 19.99 mS/cm ;
… to 199.9 mS/cm
Resolution0.001 µS/cm ; 0.01 µS/cm ;
0.1 µS/cm ; 1 µS/cm ;
5 µS/cm ; 0.01 mS/cm ;
0.1 mS/cm
Accuracy±1 % full scale reading
Cell Constant0.01 ; 0.1 ; 1 ; 10
Temperature
Range-9.9 to 125 ºC
Resolution0.1 ºC
Accuracy±0.5 ºC
SensorPt100 / Pt1000 (jumper selectable)
CompensationAuto/manual (normalized at 25 ºC)
CoefficientUltrapure water or linear 0.00 to 10.00 %
Set Point and Controller Functions
Set Point 1 (SP1) /
Set Point 2 (SP2)
… to 1.999 µS/cm or … to 19.99 µS/cm or
… to 199.9 µS/cm or … to 5000 µS/cm or
… to 19.99 mS/cm or … to 199.9 mS/cm
Switching Conductivity Hysteresis0 to 10 % of full scale
Function (Switchable)P control (pulse length/pulse frequency); limit control
Adjustable Period With Pulse Length Controller
0.5 to 20 sec
Adjustable Period With Pulse Frequency Controller60 to 120 pulse/min
Pickup/Dropout Delay0 to 2000 sec
Contact Outputs3 SPDT relays
Switching Voltage/
Current/Power
Max. 250 VAC / max. 3 A / max. 600 VA
Alarm Functions
Function (Switchable)Steady or fleet (pulse)
Wash Cycle
0.1 to 199.9 hr
Wash Duration1 to 1999 sec
Pickup Delay0 to 2000 sec
Switching Voltage/
Current/Power
Max. 250 VAC / max. 3 A / max. 600 VA
Electrical Data and Connections
Transmitter function0/4 to 20 mA scalable outputs for Conductivity,
galvanically isolated
Hold function switchTo freeze output current and deactivate control relays
LoadMax. 600 Ohm
Conductivity input2-pin terminal
Connection terminal5-pole, 17-pole terminal, detachable blocks
Power Supply
Input110 VAC
(jumper selectable) ;
48 to 62 Hz ; max. 7 VA
(For TSCONCTP1001)
220 VAC
(jumper selectable) ;
48 to 62 Hz ; max. 7 VA
(For TSCONCTP1002)
Main FuseSlow-blow 250 V / 100 mA
Pollution Degree2
Transient Overvoltage CategoryII
EMC Specifications
Emitted InterferenceAccording to EN 50081-1
Immunity to InterferenceAccording to EN 50082-1
Environmental Conditions
Operating temperature range-10 to 50 ºC
Max. relative humidity80 % up to 31 ºC decreasing linearly to 50 % at 40 ºC
Mechanical Specifications
Dimensions (WxHxD)96 x 96 x 175 mm
Weight700 g (unit) / 800 g (packed)
Ingress protectionIP54 (front panel)